Description
Altern DC Hipot Tester adopts high frequency Pulse Width Modulation (PWM) technology to make closed adjustment with high voltage stability, small ripple factor and fast reliable protection circuit. The wide temperature LCD screen adopts green back light, which enables clear display either in bright light or in darkness. High-pressure components use Dupont new filling material, making the product more stable and reliable. Products are widely used in electricity power supply departments, power transmission and transformation engineering company and preventive test of large industrial enterprises and scientific research institutes as regulated dc high voltage power supply.
Features
Specification
|
Voltage (KV)/mA |
Control Box |
High-Voltage Transformer |
|||
|
Rated Voltage |
Dimension(mm) |
Weight(kg) |
Dimension(mm) |
Weight(kg) |
|
|
60/2-5 |
60KV |
310 * 250 * 230 |
5kg |
470 * 260 * 220 |
6kg |
|
80/2-5 |
80KV |
310 * 250 * 230 |
6kg |
490 * 260 * 220 |
8kg |
|
100/2-5 |
100KV |
310 * 250 * 230 |
6kg |
550 * 260 * 220 |
8kg |
|
120/2-5 |
120KV |
310 * 250 * 230 |
7kg |
600 * 260 * 220 |
10kg |
|
200/2-5 |
200KV |
310 * 250 * 230 |
8kg |
1000 * 280 * 270 |
20kg |
|
300/2-5 |
300KV |
310 * 250 * 230 |
9kg |
1300 * 280 * 270 |
22kg |
|
Output Polarity |
Negative polarity, no-voltage start, linear continuous adjustment |
||||
|
Operation Voltage |
50HZ AC220V±10% |
||||
|
Voltage Error |
0.5%±2, minimum solution 0.1KV |
||||
|
Current Error |
0.5%±2, minimum solution 0.1µA |
||||
|
Ripple Factor |
better than 0.5% |
||||
|
Voltage Stability |
Random fluctuation , grid change is 10% , the fluctuation <=0.5% |
||||
|
Working Manner |
Interval working, less than 30 minutes under rated load |
||||
|
Temp. & Humidity |
Temperature: 0-40℃ , humidity: less than 90% |
||||
|
Storage |
Temperature: -10℃ ~40℃ , humidity: less than 90% |
||||
|
Altitude |
Lower than 3000 m |
||||